Overview
The voltage signal sensor is specially designed for power supply monitoring for fire equipment in accordance with national standard GB28184-2011 "Power supply monitoring system for fire protection equipment". When the power supply for fire protection equipment fails (interruption, overvoltage, undervoltage, phase loss, etc.), the sensor will upload the fault alarm data and measurement data to the fire protection equipment power monitor through the communication interface.
Technical parameter table
| Models and specifications | TY-DY-3VE | TY-DY-6VE | TY-DY-6VE | TY-DY-9VE |
| Detection object | One way of three-phase voltage | Two ways of three-phase voltage | Six ways of single-phase voltage | Three ways of three-phase voltage |
| Rated power | <0.3W | |||
| Communication mode | Non-polarity two-bus | |||
| Cable specification | NH-RVS-2×2.5mm² | |||
| Address code | Each sensor has a unique address code | |||
| Ambient temperature | -15℃~55℃ | |||
| Ambient humidity | Relative humidity ≤ 95% | |||
| Altitude | <2000m | |||
| IP rating | IP30 | |||
| Outline dimensions | 70×63×85mm (L × W × H) | |||
| Status indicators | Blinks during an inspection. The yellow indicator is steadily on when a fault condition occurs. | |||
| Operating voltage | Undulating voltage 18 V to 26 V | |||